Low Voltage Back
 

 

 

 

 
 
Home  >> Products >> Low Voltage >> Magnetic Starter & Thermal Relay >> JR-SS Electronic Overload Relay
 

 

 

1.Application
 
JR-SS electronic overload relay is suitable for AC 50/60Hz, voltage up to 600VAC and currentup to 60A. It is used as overload and phase loss protection, independently adjustable startingand trip delay, visual current setting aid and trip indication, fail safe protection (N type) andelectronic shear pin function. The product conforms to IEC60947-1 standard.
 
 
2. Specification
 
Type JR-SS
Current range 05)0.5-5A(scale 6.5A)
30)3-30A(scale 35A)
60)5-60A(scale 70A)
Rated voltage 600VAC,50/60Hz
Operation setting D-TIME 0.2-30seconds
O-TIME 0.2-10seconds
Accuracy Current ±10%
Time ±15% of max.time set value
Time characteristics Definite time
Control voltage
220)Voltage free(90~260)VAC,50/60Hz
440)Voltage free(320~480)VAC,50/60Hz
Other voltage optional.
Current sensing 2 CTs
Output contacts Contacts SPDT 3A/250VAC Resistive
Condition N Type Normally energized:95-| |-98closed
R Type Normally De-energized:95-|/|-98closed
Reset Manual or remote electrical by interrupting supply
Environment Temp. Run Run -20+70 deg.OC
Store -30+80 deg.OC
Humidity 45~85% RH,non-condsing
Insulation Between casing and circuits:Over 10MΩ with DC 500V megger
Dielectric strength
1)Between casing & circuits:AC 2000V,60Hz,1 min
2)Between contacts:AC 1000V,60Hz,1 min
3)Between contacts:AC 2000V,60Hz,1 min
Power consumption Under 2W
Mounting 35mm Din Rail(D)
The run-up current of motor(starting current)does relay trip because over current protection of JR-SS is not applied during motor run-up time.

 

 

  Back